GIL High Current Main Busbar Enclosure

GIL High Current Main Busbar Enclosure is designed for high-capacity power transmission scenarios, used to withstand high rated current and short-circuit impacts, and to achieve insulated gas containment, circuit shielding, and reliable grounding. This product is a drawing-customized component with no standard spot stock.
Send Inquiry
Description

Cangzhou Jianbo Electric Power Equipment Co., Ltd. is one of the most reliable manufacturers and suppliers of gil high current main busbar enclosure in China. With abundant experience, we are committed to providing high quality customized service for global clients. If you're going to buy bulk gil high current main busbar enclosure made in China, welcome to get free sample from our factory.

 

Product Name

GIL High Current Main Busbar Enclosure

Shell Material

Aluminum Alloy 5083-H112, 6061-T6

Plate Thickness

3–20mm, selected based on design pressure and short-circuit condition calculations

Applicable Large Diameter Range

φ600–φ1400mm, adapted to high-capacity current-carrying requirements

Short-Circuit Resistance Design

Shell structure machined and verified according to short-circuit electrodynamic load

Maximum Single Section Length

Up to 10m, balancing rigidity and transportation limits

Welding Control

Longitudinal and circumferential welds executed with 100% non-destructive testing

Mandatory Factory Inspection Items

Hydrostatic strength test, helium mass spectrometer leak detection, non-destructive testing of critical welds

 

GIL High Current Main Busbar Enclosure is designed for high-capacity power transmission scenarios, used to withstand high rated current and short-circuit impacts, and to achieve insulated gas containment, circuit shielding, and reliable grounding. This product is a drawing-customized component with no standard spot stock. It adopts a thickened aluminum alloy shell body, focusing on enhancing shell rigidity, controlling structural deformation and temperature rise under high current, and can be pre-fabricated with temperature monitoring, grounding, and expansion joint installation bases. Only the metal shell body is delivered, excluding internal electrical components such as conductors and insulators. It is suitable for main transformer outgoing lines, high-capacity utility tunnel power transmission, and high-load overseas EPC projects.

 

Product Advantages

 

① Reinforced Shell Rigidity to Withstand Short-Circuit Electrodynamic Impact

The shell structure is optimized for high-current short-circuit impact loads, reducing the risk of shell deformation caused by instantaneous electrodynamic forces and ensuring structural integrity under system fault conditions.

② Optimized Structural Design to Suppress Operating Temperature Rise

Matching the heat dissipation requirements of high-capacity circuits, the shell cross-section and wall thickness are reasonably designed to reduce eddy current heating effects and maintain long-term full-load operation stability.

55
64

③ High-Precision Welding and Forming to Ensure Large-Diameter Roundness

Relying on large-scale rolling and welding fixtures, the roundness of large-diameter shells and the coaxiality of flanges are strictly controlled, reducing assembly misalignment and ensuring internal component installation clearance.

④ Full Inspection of Critical Welds for High-Reliability Engineering

Critical welds are executed with 100% non-destructive testing, controlling quality from the welding stage to meet the stringent reliability requirements of main circuit high-capacity power transmission.

⑤ Integrated Pre-Fabrication of Functional Bases

Temperature monitoring interfaces, grounding terminals, and expansion joint supports are all pre-fabricated and welded in-house, avoiding on-site hot work modification to the shell base material.

90

Product Applications

 

 

1. Main Transformer Outgoing Circuit: High-capacity GIL main circuit between substation main transformer and switchgear.

2. High-Capacity Underground Utility Tunnel Projects: GIL pipeline enclosures with large transmission capacity in urban utility tunnels.

3. Pumped Storage and Thermal Power High-Capacity Outgoing Lines: High-load power transmission main sections in power stations.

4. Large-Scale Domestic and Overseas EPC Projects: Outsourced enclosures for high rated current level GIL engineering projects.

5. Power Station Capacity Expansion and Retrofit: Upgrading transmission capacity by replacing original small-specification busbar enclosures.

 

 

FAQ

 

 

Q1: What is the main difference between a high-current enclosure and a standard main busbar shell?

A: The high-current enclosure focuses on short-circuit electrodynamic forces and temperature rise suppression. The shell wall thickness, rigidity, and diameter are all designed according to high-capacity operating conditions, and the overall structural strength requirements are higher than those of conventional GIL enclosures.

Q2: What information is needed for inquiry?

A: Provide drawings or 3D models, specifying rated current, short-circuit parameters, design pressure, single section length, inspection level, and purchase quantity to facilitate a complete evaluation.

Q3: Can the large-diameter shell be made as an extra-long single section?

A: Limited by transportation and rigidity conditions, there is an upper limit to the single section length. For extra-long pipelines, reasonable segmentation is required. We will provide segmentation suggestions that balance performance and logistics. Under conventional domestic transportation conditions, the single section is recommended not to exceed 12m.

Q4: Can temperature sensor installation interfaces be added?

A: Yes. Temperature monitoring bases and openings are all pre-fabricated in the factory. On-site opening is not recommended.

 

Factory Advantages

 

 

1. Equipped with large-diameter thick-wall shell rolling and roundness correction fixtures, meeting the manufacturing requirements for shell rigidity and roundness under high-current conditions.

2. Rolling, welding, non-destructive testing, pressure and air-tightness tests are all completed in-house in a closed loop, with no outsourcing of critical processes.

3. Possessing the process evaluation capability for short-circuit loads and temperature rise of high-current GIL enclosures, providing process optimization suggestions before production.

4. Capable of undertaking single-piece trial production and project bulk supply, with unified process standards for both samples and mass production.

5. Complete drawing archive management facilitates later spare part production and meets the long-term operation and maintenance needs of large-scale power stations.

Hot Tags: GIL high current main busbar enclosure, China GIL high current main busbar enclosure manufacturers, suppliers, factory

Send Inquiry

Send Inquiry