Cangzhou Jianbo Electric Power Equipment Co., Ltd. is one of the most reliable manufacturers and suppliers of single-seal gis circuit breaker pd test tank in China. With abundant experience, we are committed to providing high quality customized service for global clients. If you're going to buy bulk single-seal gis circuit breaker pd test tank made in China, welcome to get free sample from our factory.
Single-seal GIS Circuit Breaker PD Test Tank is a dedicated test chamber built to simulate real GIS gas-compartment environment for circuit-breaker unit partial-discharge and high-voltage withstand test. This GIS-integrated PD test tankadopts single-seal flange for basin-insulator mating, it can connect with standard GIS basin insulator to separate test zone from external high-voltage test space.
Different from standalone open test tanks, this single-seal GIS breaker partial-discharge test chamber reproduces actual mechanical and gas boundary conditions same as real GIS bay. It is used for type-test and R&D evaluation of breaker units that will be assembled inside GIS equipment. Every finished SF6 GIS test enclosure completes hydrostatic pressure test, single-seal flange helium sniff scan, weld NDT and inner-cavity particle-removal cleaning before shipment. Target buyers: GIS original manufacturers, high-voltage R&D labs, third-party electrical test institutes, switchgear component suppliers.
|
Product Name |
Single-seal GIS Circuit Breaker PD Test Tank |
|
Main Material |
Aluminum alloy / Carbon-steel |
|
Applicable Standards |
IEC 60270,IEC 62271-203,GB/T7354-2018,GB/T7674 |
|
Rated Test Voltage |
72.5kV-252kV (per customer drawing) |
|
Seal-structure |
Single-groove single-seal flange for GIS basin-insulator mating |
|
Key interface |
Standard GIS basin-insulator mounting flange, SF₆ filling port, PD coupling-sensor port, pressure monitoring port |
|
Welding Process |
Automatic TIG welding |
|
Mandatory In-house Tests |
Hydrostatic pressure test;Single-seal flange targeted helium sniff-scan;UT & radiographic weld inspection;Inner-cavity particle-removal cleaning inspection |
Core Product Advantages
① Real GIS boundary simulation with basin-insulator interface
This Single-seal GIS Circuit Breaker PD Test Tank comes with standard single-seal flange for GIS basin insulator. You can mount real basin insulator to divide gas zones. Test environment matches actual GIS bay condition, so PD test data is closer to real-site operating performance.
② Single-seal flange optimized for repeated insulator swap
The single-seal mating groove on GIS-integrated PD test tank is one-time CNC machined. It tolerates repeated installation & removal of basin insulators during multiple R&D test cycles. Seal-groove dimension keeps consistent after many times of assembly and disassembly.


③ Strict inner-cavity particle removal to suppress stray PD
Inner cavity of single-seal GIS breaker partial-discharge test chamber goes through burr removing, chip sweeping and particle inspection. Loose metal particles are eliminated. It reduces stray partial-discharge noise generated by test tank itself and avoids misjudging test sample PD signals.
④ Reserved PD coupling-sensor port for GIS-style measurement
This SF6 GIS test enclosure reserves dedicated mounting port for GIS-type partial-discharge coupling sensor. No need for on-site cutting or welding. Users can adopt same PD measuring method used on real GIS equipment for lab evaluation.
⑤ Targeted helium sniff-scan on basin-insulator single-seal face
We focus helium sniff-scan on the critical single-seal flange for basin insulator, besides regular weld inspection. Hidden micro-leaks on insulator mating surface are caught before delivery. Reduce unexpected SF6 gas loss during long-time PD type-test.

FAQ
Q1: What grounding requirements shall we follow for this Single-seal GIS Circuit Breaker PD Test Tank during PD testing?
The test tank shell must implement reliable protective earth connection following high-voltage test standards. Multi-point grounding is recommended. Loose or thin-gauge ground conductors are prohibited. Poor grounding brings external electromagnetic noise and distorts partial-discharge reading.
Q2: Does this GIS-simulating PD test tank come with builtin lifting lugs for whole-unit relocation?
Lifting lugs can be fabricated per your drawing specification. Without explicit requirement, only bare shell will be delivered without lifting structure. Never sling the tank via welding seams or flange edges for hoisting and moving.
Q3: What SF₆ gas pre-handling advice before injecting gas into this PD test tank?
Use certified dry SF₆ gas with moisture content complying with IEC limits. Wet or impure gas will trigger extra stray partial-discharge noise and speed up oxidation of the tank's inner metal surfaces.
Q4: Is this test tank applicable for cross-reference test among several different breaker prototypes?
Yes, provided all prototype outer dimensions fit tank inner space. Critical note: full innercavity cleaning must be completed when switching test samples, to prevent residual debris from contaminating subsequent test results.
Q5: How to maintain the basin-insulator single-seal flange during long-term idle storage?
Keep custom-fit flange protective covers installed throughout storage period. Protect seal grooves from dust, dampness and mechanical scratches. Remove protective covers only right before formal test assembly.
Q6: Will inner-cavity surface degrade after numerous cycles of PD tests and SF₆ gas fill-and-vent operations?
Inner-surface condition remains stable with qualified gas and normal test conditions. Repeated in-chamber arc events will produce solid residues. If arc faults frequently occur during testing, innercavity full cleaning is required before next test batch.
Hot Tags: single-seal GIS circuit breaker pd test tank, China single-seal GIS circuit breaker pd test tank manufacturers, suppliers, factory