Cangzhou Jianbo Electric Power Equipment Co., Ltd. is one of the most reliable manufacturers and suppliers of gis branch enclosure in China. With abundant experience, we are committed to providing high quality customized service for global clients. If you're going to buy bulk gis branch enclosure made in China, welcome to get free sample from our factory.
GIS Branch Enclosure is an airtight component for busbar branching in GIS gas chambers, adopting a main pipe with a single side branch structure and fitted with an internal SF₆ gas cavity. Compared with three-way T-enclosures and dual-seal versions, it boasts a simpler structure, fewer sealing points and higher cost efficiency. Having undergone standard process inspection, it also serves as a grounded shield and is suitable for conventional single-branch tapping scenarios.
|
Product Name |
GIS Branch Enclosure |
|
Base material |
6061-T6 aluminum alloy (customizable) |
|
Manufacturing process |
Automatic argon arc welding + integral CNC machining + surface anti-corrosion treatment |
|
Main structure |
Main cylinder + side single branch, with sealing butt flanges at both ends of the main pipe |
|
Branch angle |
Standard 90°orthogonal, customizable oblique angles available |
|
Design pressure |
Standard 0.6–0.8 MPa, higher pressure rating customizable |
|
Sealing type |
Single standard sealing ring groove embedded in flange, meets low-leakage requirements for SF₆ gas chambers |
|
Surface finish |
Anodized / as-machined finish; spray coating for outdoor applications available on request |
|
Applicable voltage range |
110kV–550kV |
Core Product Advantages
① Concise structure, cost-effective universal solution
The regular main pipe + side branch structure has a single interface and fewer sealing points for easy assembly and disassembly. It is a standard universal solution for single-branch tapping in GIS systems with controllable cost.
② Integral machining, reliable sealing performance
Finished in one clamping setup after welding assembly, all flange faces are precision ground with standard sealing grooves. Matched with O-rings and evenly distributed bolts, it ensures continuous gas flow between main and branch pipes, with SF₆ leakage rate stably meeting industry standards.


③ Smooth transition, excellent insulation performance
The joint between branch and main pipe is formed with large-radius arc transition, featuring a smooth inner wall without sharp edges to avoid electric field concentration and suppress partial discharge. Built-in insulator positioning steps ensure accurate alignment of conductive components.
④ Lightweight yet high strength, fully customizable
Fabricated from 6061-T6 aluminum alloy by welding, it balances structural strength and light weight to meet pressure and short-circuit force requirements of GIS gas chambers; material upgrade is available for high-voltage large-bore scenarios. Dimensions such as bore size, angle and flange standard can be customized per drawings, with consistent batch quality.
Applications
- Single-point busbar tapping for 110kV–550kV GIS gas-insulated switchgear main busbars
- Connection transition between single bays (feeder bay, voltage transformer bay, surge arrester bay, etc.) and the main gas chamber
- Branch gas chamber expansion and equipment interfacing for hybrid gas-insulated switchgear (HGIS)
- Standard branch nodes for conventional bay expansion and circuit renovation in substation GIS systems
- Single-branch circuit extension for GIS stations in industrial, mining and municipal distribution applications
Installation Instructions
1. Inspection and cleaning
Verify product identification against drawings. Inspect the cylinder, flange sealing faces, sealing grooves and bolt holes for damages or burrs. Clean impurities on the inner wall and sealing faces.
2. Seal assembly
Install O-rings into the sealing grooves and apply an appropriate amount of vacuum silicone grease. Mount insulators and conductor bars on the inner positioning steps per drawings, then align the flange faces after confirming correct position.
3. Symmetrical tightening
Tighten all flange bolts crosswise and evenly to the specified torque in 2–3 increments, to ensure uniform fitting of sealing faces and prevent leakage caused by uneven pressure.
4. Air tightness verification
Fill with SF₆gas for leak detection test. After passing the test, conduct withstand voltage and partial discharge tests, and record the gas chamber parameters.
After-sales Service
Complete documentation with full traceability
Full set of reports including dimension inspection, sealing accuracy and air tightness are delivered with the goods for full process traceability.
Transparent process with inspection support
Process footage of key procedures can be provided for customers to verify sealing surface finish, transition corner accuracy and weld formation quality.
Prompt response and proper handling
Timely response and verification for dimension or process objections; rework or replacement will be arranged for manufacturing quality issues (non-human or non-installation damage).
Full technical support throughout the process
Assistance is available for issues related to docking, assembly and testing, with on-site installation guidance provided.
Hot Tags: GIS branch enclosure, China GIS branch enclosure manufacturers, suppliers, factory